What are the requirements for the configuration of fire extinguishers in industrial areas?

Boiler

  • Type of fire. Mainly solid fires, gas fires, but also the presence of oil, electrical and dust fires.
  • configuration principles. Fire extinguishers to dry powder ABC fire extinguishers (need a certain amount of cart-type fire extinguishers), but also equipped with carbon dioxide fire extinguishers, and must be set up fire hydrant. Pot household area of each layer according to the maximum protection distance of fire extinguishers in sufficient quantities, set point should be kept within 30m of the operator use.

Steam turbine

  • Type of fire. Solid fires, gas fires, oil fires and electrical fires, etc.
  • configuration principles. Fire extinguishers to dry powder ABC fire extinguishers (need a certain amount of cart-type fire extinguishers), but also equipped with carbon dioxide fire extinguishers, and must be set up fire hydrant. In principle, each layer in the steam engine room area in accordance with the maximum protection distance of fire extinguishers in sufficient quantities, set point should be kept within 30m of the operator use; steam engine room oil system area shall be placed 2 dry powder cart fire extinguishers; turbine platform (car surface) area needs to be placed 2 boxes of carbon dioxide fire extinguishers.

Electrical

  • Type of fire. Solid fires and electrical fires, etc.
  • configuration principles. Fire extinguishers mainly carbon dioxide (need a certain amount of cart-type fire extinguishers), can also be equipped with dry powder or foam fire extinguishers. Switch room, the main, plant transformers and other electrical areas should be placed 1 box of carbon dioxide fire extinguishers and 1 carbon dioxide cart fire extinguishers; set control building should be placed 6 boxes of carbon dioxide fire extinguishers.

Oil depot

  • Fire type. Oil fire.
  • configuration principles. Equipped with clear water foam and dry powder fire extinguishers, equipped with cart dry powder ABC fire extinguishers according to the actual situation.

periphery

Fire extinguishers can be reasonably configured according to the site construction and the type of fire that may occur. Usually temporary facilities area, every 100m² equipped with two 10L fire extinguishers; temporary carpentry room, paint room and wood, machine tools room, etc., every 25m² should be configured with a suitable type of fire extinguisher; oil depot, dangerous goods warehouse should be equipped with a sufficient number of fire extinguishers; warehouse or stockyard, should be arranged in accordance with the characteristics of the fire object, grouping acid and alkali, foam, water and carbon dioxide fire extinguishers, each group of fire extinguishers should not Less than 4, the distance between each group of fire extinguishers should not be greater than 30m.